Configuration & Basic Operation

3-29

Setting the Hysteresis

Operating Procedure

The third part of the example is to configure the hysteresis to 2.0

°

C.

1.

Press the

O

key to move from the Operation function group to the

Adjustment function group.

Figure 3.50

Figure 3.51

2.

The Adjustment function group Display parameter will be displayed in
the adjustment function group.

Figure 3.52

3.

Select the Hysteresis (Heating) parameter by pressing the

M key.

Figure 3.53

4.

Press the

U and D keys to set the hysteresis (2.0 in this example).

Either press the

M key or wait for at least 2 seconds after setting the

hysteresis value to load the new value into controller memory.

Figure 3.54

5.

To return to the Operation function group, press the

O

key for at least

1 second.

C

25

200

PV

1.adj

Adjustment
Display

hys

1.0

Hysteresis
(heating)

C

hys

2.0