Rockwell Automation 900-TC32 Digital Temperature Controllers, Series B User Manual

Page 109

Advertising
background image

Publication 900-UM007D-EN-E - January 2011

Configuration & Basic Operation

3-39

4.

Press the

M key to select rt (Robust Tuning).

Figure 3.76

5.

Press the

U key to select on. off is the default.

Figure 3.77

6.

To return to the Initial Setting function group, press the

O

key for at

least 1 second.

7.

To return to the Operation function group, press the

O

key for at least

1 second.

Figure 3.78

Manual PID Setup

The individual P, I, and D values can be manually set in the Proportional Band,
Integral Time, and Derivative Time parameters in the Adjustment function
group.

EXAMPLE

Operation Procedure

In this example, the Proportional Band parameter will be configured to 10.0,
the Integral Time parameter will be configured to 250, and the Derivative
Time parameter will be configured to 45.

rt

off

RT

rt

on

C

25

100