Publication 900-UM007D-EN-E - January 2011

4-52

Parameter Adjustments & Application Considerations

5. Press the D key to enter the password (−169), and move from the

Initial Setting function group to the Advanced Setting function group.

Figure 4.101

6. Select the LBA Detection Time parameter by pressing the M key.

Figure 4.102

7. Press the U key to set the parameter to 10.

Figure 4.103

8. Select the LBA Level parameter by pressing the M key.

Figure 4.104

9. Press the U key to set the parameter to 8.0. (Note: The default is 8.0.)

10. Select the LBA Band parameter by pressing the M key.

Figure 4.105

11. Press the U or D key to set the parameter to 3.0. (Note: The default is

3.0.)

Figure 4.106

init

off

Parameter
initialization

lba

0

LBA detection
time

C

lba

10

C

lbal

8.0

LBA level

C

lbal

8.0

C

lbab

3.0

LBA band

C

lbab

3.0