Rockwell Automation 900-TC32 Digital Temperature Controllers, Series B User Manual

Page 186

Advertising
background image

Publication 900-UM007D-EN-E - January 2011

4-50

Parameter Adjustments & Application Considerations

Determining the LBA Detection Time

To manually configure the LBA detection time, configured the LBA Detection
Time parameter to twice the LBA reference time given in the example below.

EXAMPLE

Procedure

1. Set the output to the maximum value.

2. Measure the time required for the change in the input to reach the LBA

band.

Figure 4.95

3. Set the LBA Detection Time parameter to two times the measured time.

LBA Level

Configure the control deviation when the control loop is working properly.

The default is 8.0 (

°C/°F) for Controllers with Thermocouple/Resistance

Thermometer Multi-Inputs and 10.00% FS for Controllers with Analog
Inputs.

LBA Band

There is assumed to be an error in the control loop if the control deviation is
greater than the threshold configured for the LBA Level parameter and if the
control deviation does not change by at least the value configured for the LBA
Band parameter.

The default is 3.0 (

°C/°F) for Controllers with Thermocouple/Resistance

Thermometer Multi-Inputs and 0.20% FS for Controllers with Analog Inputs.

MV = 100%

PV

Temperature

Time

Measurement time
Tm

LBA band

LBA detection time = Tm

Ч

2

Advertising