Rockwell Automation 900-TC32 Digital Temperature Controllers, Series B User Manual

Page 20

Advertising
background image

Publication 900-UM007C-EN-E - January 2011

P-vi

Preface

900-TC8, 900-TC16, &
900-TC32 Ratings

Characteristics

Table P.E — 900-TC8, 900-TC16, & 900-TC32 Ratings

Series A

Series B

Input sensor types for thermocouple inputs

---

The following types of thermocouple input
were added: W and PLII.

Input range for E thermocouple: 0...600 ºC

Input range increased for E thermocouple:
-200...600 ºC

Input accuracy

• Thermocouple: ±0.5% PV or ±1ºC,

whichever is greater) ±1 digit

• Platinum resistance thermometer:

(±0.5%PV or ±1ºC, whichever is
greater) ± 1 digit

• Analog input: ±0.5% FS ± digit

• Thermocouple: ±0.3% PV or ±1ºC,

whichever is greater) ±1 digit

• Platinum resistance thermometer:

(±0.2%PV or ±.08ºC, whichever is
greater) ± 1 digit

• Analog input: ±0.2% FS ± digit

Influence of signal source resistance

• Thermocouple: 0.1ºC/

Ω (except B,

R, S), 0.2ºC/

Ω (B, R, S)

• Platinum resistance thermometer:

0.4ºC/

Ω

• Thermocouple: 0.1ºC/

Ω (for all

specifications)

• Platinum resistance thermometer:

0.1ºC/

Ω

Current outputs

• Current output resolution, approx.:

2,700

• Current output resolution, approx.:

10,000

Alarm outputs

• 250 VAC, 1A (900-TC16 & 900-TC32)

• 250VAC, 3A (900-TC16)
• 250VAC, 2A (900-TC32)

Table P.F — Characteristics

Series A

Series B

Front Panel
(900-TC8)

---

PV Status Display

PF Key Added

---

PV/SP display selection for
three-level display

Inputs

---

Square root extraction (for models
with analog inputs)

PF Key

Advertising