Parameter Adjustments & Application Considerations

4-21

2. Select Move to Advanced Setting function group by pressing the

M

key.

Figure 4.34

3. Press the

D

key to enter the password (–169) to cancel protection. You

can now move to the Advanced Setting function group by pressing the

M

key or leaving the setting for at least 2 seconds.

Figure 4.35

Figure 4.36

4. Select Number of Multi-SP Uses parameter by pressing the

M

key.

Figure 4.37

5. Press the

U

key to set the parameter to 2. This allows set point change

from event input (refer to Table 4.F).

Figure 4.38

6. To return to the Initial Setting function group press the

key for at

least 1 second.

7. To return to the Operation function group press the

key for at least

1 second.

Set Points 0, 1, 2, and 3 are selected according to the ON/OFF states of Event
Inputs 1 and 2.

in-t

5

Input type

amov

-169

init

off

Parameter
initialization

ev-m

1

Number of
multi-SP uses

ev-m

2