Publication 900-UM007D-EN-E - January 2011

Calibration

C-13

Figure C.22

5. Press the M key to display the count value for each Input Type. The

No. 2 display at this time displays the currently entered count value in
Hexadecimal. Set the 6-dial as follows:

• Input Type 0: 390 Ω
• Input Type 1, 2, 3 or 4: 280 Ω

Figure C.23

6. Allow the count value on the No. 2 display to fully stabilize, then press

the

D key to temporarily register the calibration setup. If this count

value is outside of the specified range, the No. 2 display will flash and
the count value will not be temporarily registered.

7. Press the M Key to display the count value for each input type. The No.

2 display at this time shows the currently entered count value in
hexadecimal.Set the 6-dial as follows:

• Input type 0: 200 Ω
• Input type 1, 2, 3 or 4: 140 Ω

Figure C.24

8. Allow the count value on the No. 2 display to fully stabilize, then press

the

D key to temporarily register the calibration setup.

If this count value is outside of the specified range, the No. 2 display will
flash and the count value will not be temporarily registered.
When the

M key is pressed, the status changes as shown in Figure

C.25. Set the 6-dial to 10

Ω.

9. Allow the count value on the No. 2 display to fully stabilize, then press

the

D Key to temporarily register the calibration settings.If this count

value is outside of the specified range, the No. 2 display will flash and
the count value will not be temporarily registered.

adj

30

p280

e26b

Input Type

1, 2, 3, 4:

p390

e20c

Input Type

0:

p200

93a7

p140

e26b