Rockwell Automation 900-TC32 Digital Temperature Controllers, Series B User Manual
Page 83

Publication 900-UM007D-EN-E - January 2011
Configuration & Basic Operation
3-13
✟ The non-contact infrared sensor must be configurable for a Type K thermocouple output within either of the
four specified ranges. For example, in Omron ES1B or Calex EL Series (Convir) infrared sensor.
• The default is 5 (shaded).
• If an RTD is mistakenly connected while a setting for other than a
platinum resistance thermometer is in effect, the controller error code
s.err will be displayed. To clear the s.err display, check the wiring
and then turn the controller power OFF and back ON.
Table 3.C — List of Global Temperature (GT) Input Types
Input Type
Specifications
Set Value
Input Temperature Setting Range
ControllerType
with
Thermocouple
and Resistance
Thermometer
(RTD)
Multi-input
Platinum Resistance
Thermometer (RTD)
Pt100
0
−200…850 (°C)/−328…1,562 (°F)
1
−199.9…500.0 (°C)/−327.8…932.0 (°F)
2
0.0…100.0 (
°C)/32.0…212.0 (°F)
JPt100
3
−199.9…500.0 (°C)/−327.8…932.0 (°F)
4
0.0…100.0 (
°C)/32.0…212.0 (°F)
Thermocouple
K
5
−200…1,300 (°C)/−328…2,372 (°F)
6
−20.0…500.0 (°C)/-4.0…932.0 (°F)
J
7
−100…850 (°C)/−148…1,562 (°F)
8
−20.0…400.0 (°C)/-4.0…752.0 (°F)
T
9
−200…400 (°C)/−328…752 (°F)
10
−199.9…400.0 (°C)/−327.8…752.0 (°F)
E
11
-200…600 (
°C)/-300…1,100 (°F)
L
12
−100…850 (°C)/−148…1,562 (°F)
U
13
−200…400 (°C)/−328…752 (°F)
14
−199.9…400.0 (°C)/−327.8…752.0 (°F)
N
15
−200…1,300 (°C)/−328…2,372 (°F)
R
16
0…1,700 (
°C)/32…3,092 (°F)
S
17
0…1,700 (
°C)/32…3,092 (°F)
B
18
100…1,800 (
°C)/212…3,272 (°F)
Infrared (non-contact)
temperature sensor
✟
10…70
°C
19
0…90 (
°C)/32…194 (°F)
60…120
°C
20
0…120 (
°C)/32…248 (°F)
115…165
°C
21
0…165 (
°C)/32…329 (°F)
140…260
°C
22
0…260 (
°C)/32…500 (°F)
Millivolt input
0…50 mV
23
Either of the following ranges, by scaling:
−1,999…9,999
−199.9…999.9
Thermocouple
W
24
0…2,300 (
°C)/0…3,200 (°F)
PL II
25
0…1,300 (
°C)/0…2,300 (°F)