Control by inverting direct/reverse operation, Switching 100% at execute/cancel – Rockwell Automation 900-TC32 Digital Temperature Controllers, Series B User Manual

Page 160

Advertising
background image

Publication 900-UM007D-EN-E - January 2011

4-24

Parameter Adjustments & Application Considerations

Control by Inverting Direct/Reverse Operation

When DRS (Invert Direct/Reverse Operation) is set for the Event Input
Assignment 1 or Event Input Assignment 2 parameter and the Direct/Reverse
Operation parameter is set for reverse operation, control starts with direct
operation (cooling control) when event input 1 or 2 turns ON and control
starts with reverse operation (heating control) when the event input turns
OFF.

Switching 100% AT Execute/Cancel

When AT-2 (100% AT Execute/Cancel) is set for either the Event Input
Assignment 1 or Event Input Assignment 2 parameter, 100% AT will be
executed when event input 1 or 2 turns ON and will be cancelled when the
input turns OFF.

Table 4.M

Setting

Input Contact

Program Status

Event Input 1 or 2

OFF

reset

Event Input 1 or 2

ON

Start

Table 4.N

Setting

Input
Contact

Direct/Reverse
Operation Parameter

Status

Event
Input 1 or
2

OFF

Direct operation (cooling)

Direct operation (cooling)

Reverse operation
(heating)

Reverse operation (heating)

Event
Input 1 or
2

ON

Direct operation (cooling)

Reverse operation (heating)

Reverse operation
(heating)

Direct operation (cooling)

Table 4.O

Setting

Input Contact

Status

Event input 1 or 2

OFF

100% AT cancelled

Event input 1 0r 2

ON

100% AT executed