Publication 900-UM007D-EN-E - January 2011

4-88

Parameter Adjustments & Application Considerations

Controller. The ON/OFF count alarm configured value function is disabled
by setting the ON/OFF count alarm configured value to 0.

ON/OFF Counter Reset Function

The ON/OFF counter can be reset for a specific control output.

Note: After the counter has been reset, the control output ON/OFF count

monitor value will be automatically returned to 0.

If an error occurs in the control output ON/OFF counter data, the
ON/OFF count monitor value will be configured to 9999 and an
ON/OFF count alarm will occur. The alarm can be cleared by resetting
the ON/OFF counter.

Operating Procedure

This procedure sets the Control Output 1 ON/OFF Alarm Setting parameter
to 10 (1,000 times).

1. Press the O Key for at least three seconds to move from the Operation

to the Initial Setting function group.

Figure 4.201

Table 4.AO

Parameter Name

Configurable
Range

Unit

Default

Control Output 1 ON/OFF Alarm Setting

0 to 9999

100 times

0

Control Output 2 ON/OFF Alarm Setting
(900-TC8 & 900-TC16)

0 to 9999

100 times

0

Table 4.AP

Parameter Name Configurable Range

Unit

Default

ON/OFF Counter
Reset

0: Disable the counter reset function.
1: Reset the control output 1 ON/OFF
counter.
2: Reset the control output 2 ON/OFF
counter (900-TC8 & 900-TC16).

---

0

in-t

5

Input Type