Publication 900-UM007D-EN-E - January 2011

Configuration & Basic Operation

3-61

5.

Press the

M Key to select the Heater Overcurrent Use parameter.Check

that this parameter is set to ON (the default), and then set the Heater
Overcurrent Detection 1 parameter.

Figure 3.128

Configure Overcurrent Detection

1.

Press the

O Key for at least one second to move from the Advanced

Setting function group to the Initial Setting function group. Press the

O key again for at least one second to move to the Operation function
group.

Figure 3.129

2.

Press the

O Key for less than one second to move from the Operation

function group to the adjustment function group.

Figure 3.130

3.

Press the

M Key to select the Heater Current 1 Value Monitor

parameter.Check the current value, and then modify the Heater
Overcurrent Detection parameter in step #8 to meet the requirements
of your application.

Figure 3.131

4.

Press the

M Key to select the Heater Overcurrent Detection 1

parameter. Refer to Calculating Detection Current Values when setting
the values.

Figure 3.132

ocu

on

Heater
Overcurrent
Use

C

25

100

PV/SP

l.adj

Adjustment function
group display

ct1

0.0

Heater Current
1 Value Monitor

oc1

50.0

Heater
Overcurrent
Detection 1