Rockwell Automation 900-TC32 Digital Temperature Controllers, Series B User Manual
Page 258

Publication 900-UM007D-EN-E - January 2011
5-30
Parameter Functions & Definitions
Related Parameters
Refer to the Advanced Setting function group:
• HS Alarm 1, HS Alarm 2 (page 5-31)
• HS Alarm Use (page 5-88)
• Error Displays
lcr2
Heater Burnout Detection 1 (900-TC8, 900-TC16)
Conditions of Use:
Heater Burnout (HBA) and Heater Short (HSA) alarms
and heater overcurrent detection must be supported. Alarm 1 must be
assigned. The Heater Burnout Detection parameter must be set to ON. A
single CT must be wired to the controller (single-phase heater operation).
Function:
This parameter allows you to configure the current value in amps
(A) at which the electrical Heater Burnout Alarm Output parameter becomes
active (ON).
Table 5.AF
• When the heater current value falls below the configured parameter
value, the Heater Burnout Alarm output goes ON. When the current is
equal to or greater than the value, the alarm is OFF.
• When the configured value is 0.0, the Heater Burnout Alarm is always
OFF. When the configured value is 50.0, the Heater Burnout Alarm is
always ON.
Related Parameters
Refer to the Advanced Setting function group:
• Heater Current 1 Monitor (page 5-13)
• Heater Burnout Detection, Heater Burnout Latch, Heater Burnout
Hysteresis (page 5-74)
Configurable Range
Units
Default Value
0.0…50.0
A (Amps)
0.0
hb1