Rockwell Automation 900-TC32 Digital Temperature Controllers, Series B User Manual

Page 258

Advertising
background image

Publication 900-UM007D-EN-E - January 2011

5-30

Parameter Functions & Definitions

Related Parameters

Refer to the Advanced Setting function group:

• HS Alarm 1, HS Alarm 2 (page 5-31)
• HS Alarm Use (page 5-88)
• Error Displays

lcr2

Heater Burnout Detection 1 (900-TC8, 900-TC16)

Conditions of Use:

Heater Burnout (HBA) and Heater Short (HSA) alarms

and heater overcurrent detection must be supported. Alarm 1 must be
assigned. The Heater Burnout Detection parameter must be set to ON. A
single CT must be wired to the controller (single-phase heater operation).

Function:

This parameter allows you to configure the current value in amps

(A) at which the electrical Heater Burnout Alarm Output parameter becomes
active (ON).

Table 5.AF

• When the heater current value falls below the configured parameter

value, the Heater Burnout Alarm output goes ON. When the current is
equal to or greater than the value, the alarm is OFF.

• When the configured value is 0.0, the Heater Burnout Alarm is always

OFF. When the configured value is 50.0, the Heater Burnout Alarm is
always ON.

Related Parameters

Refer to the Advanced Setting function group:

• Heater Current 1 Monitor (page 5-13)
• Heater Burnout Detection, Heater Burnout Latch, Heater Burnout

Hysteresis (page 5-74)

Configurable Range

Units

Default Value

0.0…50.0

A (Amps)

0.0

hb1

Advertising