Wiring the event input – Rockwell Automation 900-TC32 Digital Temperature Controllers, Series B User Manual

Page 65

Advertising
background image

Publication 900-UM007D-EN-E - January 2011

Preparations

2-27

Wiring the Event Input

When the appropriate option event input unit is mounted in the Bulletin
900-TC8 or 900-TC16 controller, an event input function is available by wiring
to the controllers terminals as shown in the following diagrams.

Figure 2.25

Use event inputs under the following conditions:

• The output current from the controller is approximately 7 mA @ 5V.

• Contact input ON: 1 K

Ω max., OFF: 100 KΩ min.

• Non-contact input ON: residual voltage 1.5V max., OFF: leakage

current 0.1 mA max.

Polarities using non-contact input are as follows:

Figure 2.26

900-TC16
Contact Event
Input

EV1

EV2

12

11

13

900-TC8
Contact Event
Input

EV1

EV2

A

A

A Do NOT apply an external voltage source to the Event Input Terminals

EV1

EV2

+

+

EV1

EV2

900-TC16

900-TC8

+

+

A

A

A Do NOT apply an external voltage source to the Event Input Terminals

Advertising