Out1, Control output 1 assignment – Rockwell Automation 900-TC32 Digital Temperature Controllers, Series B User Manual
Page 320

Publication 900-UM007D-EN-E - January 2011
5-92
Parameter Functions & Definitions
Related Parameters
• Process Value/Set Point (Operation function group, page 5-8)
• Alarm 1 Type (Initial Setting function group, page 5-59)
• LBA Detection Time, LBA Level (Advanced Setting function group,
page 5-90)
Control Output 1 Assignment
Conditions of Use:
The Transfer Output Type parameter must be set to OFF
when the Control Output is an analog current output.
Function:
This parameter allows you to configure the output function
assigned to Control Output 1.
Related Parameters
• Standard or Heating/Cooling (page 5-55), Program Pattern (page 5-57),
Transfer Output Type (page 5-62) (Initial Setting function group)
Table 5.DK
Control Output 1 Function
Default
None:
No control output function is assigned
o
o:
Heating control output is output
c-o:
Cooling control output is output
➊
alm1:
Alarm 1 is output
➋
alm2:
Alarm 2 is output
➋
alm3:
Alarm 3 is output
➋
p.end:
Program end is output
➋➌
ralm:
Control output ON/OFF count alarm
➋
➊
If
c-o
(cooling Control Output) is assigned for standard control, a value equivalent to 0% is output.
➋
Can be selected for relay and voltage outputs only
➌
Can be selected only when the program pattern is not set to OFF, but the function is disabled.
out1