Out1, Control output 1 assignment – Rockwell Automation 900-TC32 Digital Temperature Controllers, Series B User Manual

Page 320

Advertising
background image

Publication 900-UM007D-EN-E - January 2011

5-92

Parameter Functions & Definitions

Related Parameters

• Process Value/Set Point (Operation function group, page 5-8)

• Alarm 1 Type (Initial Setting function group, page 5-59)

• LBA Detection Time, LBA Level (Advanced Setting function group,

page 5-90)

Control Output 1 Assignment

Conditions of Use:

The Transfer Output Type parameter must be set to OFF

when the Control Output is an analog current output.

Function:

This parameter allows you to configure the output function

assigned to Control Output 1.

Related Parameters

• Standard or Heating/Cooling (page 5-55), Program Pattern (page 5-57),

Transfer Output Type (page 5-62) (Initial Setting function group)

Table 5.DK

Control Output 1 Function

Default

None:

No control output function is assigned

o

o:

Heating control output is output

c-o:

Cooling control output is output

alm1:

Alarm 1 is output

alm2:

Alarm 2 is output

alm3:

Alarm 3 is output

p.end:

Program end is output

➋➌

ralm:

Control output ON/OFF count alarm

If

c-o

(cooling Control Output) is assigned for standard control, a value equivalent to 0% is output.

Can be selected for relay and voltage outputs only

Can be selected only when the program pattern is not set to OFF, but the function is disabled.

out1