Oapt, Pmov, Move to protect function group – Rockwell Automation 900-TC32 Digital Temperature Controllers, Series B User Manual

Page 231: Operation/adjustment protection

Advertising
background image

Publication 900-UM007D-EN-E - January 2011

Parameter Functions & Definitions

5-3

Move to Protect Function Group

Conditions of Use:

The Password to Move to Protect function group

parameter must NOT be set to 0.

Function:

This parameter allows you to specify a password that must be

entered to move to the Protect function group.

• The Operation/Adjustment Protect parameter will be displayed if the

correct password is entered.

Related Parameters

• Password to Move to Protect function group (Protect function group,

page 5-5).

Operation/Adjustment Protection

Function:

These parameters specify the range of parameters to be protected.

Table 5.A shows the relationship between the configured/set values and the
range of protection.

Note:

Parameter items are not protected when the configured/set value is 0.

Table 5.A

Function Group

Configured/Set Value

0

1

2

3

Operation
Function Group

PV

PV/SP

Others

X

X

Adjustment Function Group

X

X

X

➊ Default Level of Protection: Can be displayed and changed. Can be displayed.
X

Cannot be displayed and moving to other function groups is NOT possible.

pmov

oapt