Sqrp, Using the extraction of square root parameter – Rockwell Automation 900-TC32 Digital Temperature Controllers, Series B User Manual

Page 213

Advertising
background image

Publication 900-UM007D-EN-E - January 2011

Parameter Adjustments & Application Considerations

4-77

Using the Extraction of Square Root Parameter

Extraction of Square Roots

Figure 4.167 — Extraction of Square Root Enable

• For analog inputs, the Extraction of the Square Root parameter is provided
for inputs so that differential pressure-type flow meter signals can be directly
input.

• The default setting for the Extraction of Square Root parameter is OFF. The
Extraction of Square Root Enable parameter must be configured to ON in
order to use this function.

Figure 4.168 — Extraction of Square Root Low-cut Point

• If the PV input (i.e., the input before extracting the square root) is higher
than 0.0% and lower than the low cut point configured in the Extraction of
Square Root Low-Cut Point parameter, the results of extracting the square
root will be 0.0%. If the PV input is lower than 0.0% or higher than 100.0%,
extraction of the square root will not be executed, so the result will be equal to
the PV input. The low-cut point is configured as normalized data for each
input, with 0.0 as the lower limit and 100.0 as the upper limit for the input
setting range.

Figure 4.169 —Extraction of the Square Root

sqr

off

sqrp

0.0

Argument 1 (Input Data)

Extraction of
square root

100% FS

100% FS

0

Extraction of square
root low-cut point

Advertising