5

Motor control & motor settings

5.10

Synchronous motor (SM): Pole position identification

100

Lenze · i700 servo inverter · Reference manual · DMS 1.5 EN · 03/2014 · TD05

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

How to execute the pole position identification PPI (min. movement):

1. If the controller is enabled, inhibit the controller.

Enable/inhibit operation via control word

( 59)

2. Set object

0x2825

(or

0x3025

for axis B) to "6" to change to the "Pole position identification

(min. movement)" operating mode.

3. Enable the controller to start the procedure.

Note: By means of controller inhibit, the procedure started can be cancelled any time, if

required, without a change in settings.

After successful completion of the pole position identification...
...controller inhibit is set automatically and the pole position specified in object

0x2C03:2

(or

0x3403:2

for axis B) for the activated feedback system is set.

• For permanent storage, the changed settings must be uploaded to the controller from the i700

servo inverter.
The »EASY Starter« serves to save the parameter settings of the i700 servo inverter as parameter

file (*.gdc). In the »PLC Designer«, this file can then be imported in the corresponding axis.

Saving changed parameters safe against mains failure

( 60)

• The controller inhibit automatically set by the procedure can be deactivated via the

Controlword (

0x6040

or

0x6840

for axis B).

Enable/inhibit operation via control word

( 59)

Adapt pole position identification PPI (min. movement)
The above-described procedure for pole position identification can be adjusted to the respective

machine and the prevailing moments of inertia by means of the parameters described in the

following.

Stop!

If there is no temperature monitoring in the motor and/or the I²xt motor monitoring and

the maximum current monitoring are not parameterised correctly, the motor might be

damaged permanently when the current amplitude is set too high (e.g. to the maximum

value!

Monitoring of the motor utilisation (I²xt)

( 241)

Monitoring of the ultimate motor current

( 258)