4 cia402 error codes / error messages, Error code 0x0000: no error, Error code 0x2340: short circuit on motor side – Lenze i700 User Manual

Page 267: Cia402 error codes / error messages, Chapter, List, 9diagnostics & error management

Advertising
background image

Lenze · i700 servo inverter · Reference manual · DMS 1.5 EN · 03/2014 · TD05

267

9

Diagnostics & error management

9.4

CiA402 error codes / error messages

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

9.4

CiA402 error codes / error messages

Error code 0x0000: No error

Text ID: 0x00

Error code 0x2320: Short circuit or earth leakage on motor side

Text ID: 0x04

Error code 0x2340: Short circuit on motor side

Text ID: 0x05

Error code 0x2351: Motor utilisation (I²xt) > [value] %

Text ID: 0x38

Monitoring of the motor utilisation (I²xt)

Note!

• When an error message is output, the source (device, axis A or axis B) is preceded.
• This data [value] of an error message text serves as wildcard for the value detected

during the runtime of the i700 servo inverter.

• The indices for axis A and axis B are given directly in succession in the following

descriptions for a better readability (index of axis A | index of axis B)

Cause

Remedies

Response

-

-

-

Cause

Remedies

Response

• Earth fault in motor cable.

• Excessive capacitive charging

current in the motor cable.

• Check motor cable.

• Use motor cable that is shorter or

has a lower capacitance.

Fault
Note: Error reset only possible after

5 s.

Cause

Remedies

Response

• Short circuit/earth fault in motor

cable.

• Excessive capacitive charging

current in the motor cable.

• Check motor cable.

• Use motor cable that is shorter or

has a lower capacitance.

Fault
Note: Error reset only possible after

5 s.

Cause

Remedies

Response

Motor is thermally overloaded, e.g.

due to:

• impermissible continuous

current.

• Frequent or too long acceleration

processes.

• Check drive dimensioning.

• Check setting or the warning or

error threshold.

Warning

• Warning threshold can be

adapted in

0x2D4E

|

0x354E

.

From version 01.05

, an error

response can also be parameterised

in

0x2D50:1

|

0x3550:1

.

• Error threshold can be adapted in

0x2D50:2

|

0x3550:2

.

Advertising