Lenze · i700 servo inverter · Reference manual · DMS 1.5 EN · 03/2014 · TD05

255

8

Monitoring functions

8.7

Motor phase failure monitoring

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

8.7.1

Limits of the motor phase failure monitoring

The motor phase failure monitoring can be activated for both synchronous and asynchronous

motors. However, it is possible that a current flow cannot be detected for sure in the case of certain

operating states of synchronous motors that are connected correctly. Hence, a fault is triggered. The

following table provides an overview:

Special case: Hoist
The motor phase failure monitoring may trigger a fault message in a hoist if the asynchronous

motor applied for this purpose reaches the following working point:

• The hoist moves downwards, i.e. the motor is in generator mode.
• The slip frequency equals the field frequency in terms of amount. Both frequencies mutually

neutralise themselves due to their opposite effective directions.

Subindex 4:

Motor phase failure 2: Response

Monitoring 2 (in the "operation enabled" status):

Response during activation

Selection list

(Lenze setting printed in bold)

0 No response
1 Fault
2 Warning

Write access  CINH  OSC  P  RX  TX

UNSIGNED_8

Operating status

Synchronous motor

Async. motor

Check of the motor phases prior to operation

Check of the motor phases during operation

I

q

< current threshold value

at standstill

when motor is rotating

I

q

≥ current threshold value

at standstill

when motor is rotating

Field weakening

when motor is rotating

Phase failure is detected for sure

The monitoring function may be activated without a fault pending.

I

q

Torque-forming current component

Note!

Monitoring during operation serves especially for applications which are operated with

constant load and speed. In all other cases, transient processes or unfavourable

operating points can cause maloperation.