Lenze · i700 servo inverter · Reference manual · DMS 1.5 EN · 03/2014 · TD05

127

5

Motor control & motor settings

5.12

Fine adjustment des motor model

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

7. Enter the Vp values in per cent from the grid points into the subindices of object

0x2C04

(or

0x3404

for axis B):

[5-6]

Grid point values of the saturation characteristic determined

8. Enter the maximum process current ("15 A") as maximum current in object

0x6073

(or

0x6873

for axis B).

• With these settings, the same current characteristic should occur, irrespective of the current

magnitude.

• Since the current controller gain is now corrected actively, the step responses may differ

slightly compared to the previous measurements. In this case, the current controller

parameters must be optimised one last time.

9. For permanent storage: Upload the detected characteristic from the i700 servo inverter into the

Controller.
The »EASY Starter« serves to save the parameter settings of the i700 servo inverter as parameter

file (*.gdc). In the »PLC Designer«, this file can then be imported in the corresponding axis.

Saving changed parameters safe against mains failure

( 60)

Setting for grid points 1 ... 17 in [%]

y1

y2

y3

y4

y5

y6

y7

y8

y9

y10

y11

y12

y13

y14

y15

y16

y17

137 137

137

137

137

109

92

80

68

61

53

45

37

32

26

22

19

0

6.25

12.5

18.75

25

31.25

37.5

43.75

50

56.25

62.5

68.75

75

81.25

87.5

93.75

100

I

max

[%]

Vp [%]

0

109

x2

x3

x4

x5

x6

x7

x8

x9

x10

x11

x12

x13

x14

x15

x16

x1

19

137

x17

Vp = "3.8 V/A"

100 %

º

92
80
68