Monitoring of the heatsink temperature

240

Lenze · i700 servo inverter · Reference manual · DMS 1.5 EN · 03/2014 · TD05

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

Subindex 3:

Heatsink temperature: Threshold for fan switch-on

Switch-on threshold for device fans

• If the heatsink temperature exceeds the threshold value set here, the device fan is switched on. This also

happens if the switch-off threshold is parameterised higher than the switch-on threshold by mistake.

• In order to activate the fan, the switch-on and switch-off threshold can be set to the maximum value as then the

device simultaneously switches to the "Fault" status.

• Bigger designs of the Servo-Inverter i700 are provided with an internal fan. This is triggered at the same time as

the heatsink fan and does not have internal switch-on or switch-off thresholds.

Note!

Increasing the switch-on threshold can cause higher device temperatures. This may reduce the service life of the

device!
Setting range

(min. value | unit | max. value)

Lenze setting

0.0

°C

100.0 55.0 °C

Write access  CINH  OSC  P  RX  TX

Scaling: 1/10

INTEGER_16

Subindex 4:

Heatsink temperature: Threshold for fan switch-off

Switch-off threshold for device fans

• If the heatsink temperature falls below the threshold value set here, the device fan is switched off. This only

happens if the switch-off threshold is parameterised lower than the switch-on threshold.

• Bigger designs of the Servo-Inverter i700 are provided with an internal fan. This is triggered at the same time as

the heatsink fan and does not have internal switch-on or switch-off thresholds.

Setting range

(min. value | unit | max. value)

Lenze setting

0.0

°C

100.0 45.0 °C

Write access  CINH  OSC  P  RX  TX

Scaling: 1/10

INTEGER_16