7

CiA402 device profile

7.4

Device control

188

Lenze · i700 servo inverter · Reference manual · DMS 1.5 EN · 03/2014 · TD05

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

7.4.2.8

Fault

If a grave error occurs, i.e. the drive is not able

to operate the motor in a controlled manner

anymore, the drive is switched off immediately

and this device state becomes active.

• The pulse inhibit is set, i.e. the pulses of the

controller are inhibited.

• The motor is torqueless.
• The motor brake, if available, is closed.
• The operation is inhibited.
• The inverter can be parameterised.

Bit pattern for the "Fault" device status in the Statusword (

0x6041

or

0x6841

for axis B):

Bits 15 - 8

Bit 7

Bit 6

Bit 5

Bit 4

Bit 3

Bit 2

Bit 1

Bit 0

Warning is

active

Switch on

disabled

Quick stop

Voltage

enabled

Fault active

Operation

enabled

Switched on

Ready to

switch on

X

X

0

X

X

1

0

0

0

Note!

This device status can only be left using the "

Fault reset

" command if the cause of the

fault is eliminated.

Ready to

switch on

Not ready to

switch on

Switched

on

Operation

enabled

Fault reaction

active

Fault

active

Switch on

disabled

Quick stop

active

Power on