Page 32: Supported protocols and services, Display of eoe-specific information, 0x2020, 3communication with the controller

Advertising
background image

3

Communication with the controller

3.6

Ethernet over EtherCAT (EoE)

32

Lenze · i700 servo inverter · Reference manual · DMS 1.5 EN · 03/2014 · TD05

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

3.6.2

Supported protocols and services

• ARP
• DHCP Client
• ESDCP
• ICMP (ping)
• IP
• UDP/TCP

GCI-SDO communication (TCP port 9410)

3.6.3

Display of EoE-specific information

The following object serves to read out the EoE-specific information for diagnostic purposes.

0x2020 - EoE information

From version 01.05

• The subcodes 1 ... 6 display the IP and Ethernet settings configured by the control during initialisation.

• The subcodes 7 and 8 display the traffic via EoE in Rx and Tx direction. The displayed values can be reset to "0" by

entering any value.

Sub.

Name

Lenze setting

Data type

1 Virtual MAC address

STRING(32)

2 IP address

STRING(32)

3 Subnet mask

STRING(32)

4 Default gateway

STRING(32)

5 DNS server

STRING(32)

6 DNS name

STRING(50)

7 Rx packets

UNSIGNED_32

8 Tx packets

UNSIGNED_32

Write access  CINH  OSC  P  RX  TX