0x2836 | 0x3036 - manual jog: settings, 0x2836, 0x3036 – Lenze i700 User Manual

Page 67: 0x2836:1 0x3036:1, 0x2836:3 0x3036:3, 0x2836:2 0x3036:2, 0x2836:4 0x3036:4, 0x2836:5 0x3036:5, 5motor control & motor settings

Advertising
background image

Lenze · i700 servo inverter · Reference manual · DMS 1.5 EN · 03/2014 · TD05

67

5

Motor control & motor settings

5.4

Manual control

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

Preconditions for the execution

• The motor must be able to rotate freely.
• The controller is free of errors and is in the "

Switched on

" device status.

Response of the motor during the execution
The motor rotates according to the manual jog commands.

How to activate the manual control:

1. If the controller is enabled, inhibit the controller.

Enable/inhibit operation via control word

( 59)

2. Set object

0x2825

(or

0x3025

for axis B) to "4" to change to the "Manual control" mode.

3. Enable the controller to start the manual control.

• In the »EASY Starter«, the controller can be enabled via the operator dialog for manual

control. The operator dialog also takes priority over the control word (

0x6040

or

0x6840

for axis B).

• The possible settings for the manual control mode are described in the following.

4. To stop the manual control:

• Inhibit controller.
• Set object

0x2825

(or

0x3025

for axis B) to "0" to change back to the CiA402 mode.

0x2836 | 0x3036 - Manual jog: Settings

Sub.

Name

Lenze setting

Data type

1

Manual jog: Current setpoint

30 %

UNSIGNED_16

2

Manual jog: Frequency

0.0 Hz

INTEGER_16

3

Manual jog: Ramp time - current

0 ms

UNSIGNED_16

4

Manual jog: Ramp time - frequency

500 ms

UNSIGNED_16

5

Manual jog: Time monitoring

2500 ms

UNSIGNED_32

6

Manual jog: Current controller - gain

20.00 V/A

UNSIGNED_32

7

Manual jog: Current controller - reset time

20.00 ms

UNSIGNED_32

Subindex 1:

Manual jog: Setpoint current

Selection of the current setpoint for the manual control

• 100 % ≡ rated axis current (

0x2DDF:1

or

0x35DF:1

for axis B)

Setting range

(min. value | unit | max. value)

Lenze setting

0

%

200 30 %

Write access  CINH  OSC  P  RX  TX

UNSIGNED_16

Subindex 2:

Manual jog: Frequency

Selection of the frequency for manual control
Setting range

(min. value | unit | max. value)

Lenze setting

-1000.0

Hz

1000.0 0.0 Hz

Write access  CINH  OSC  P  RX  TX

Scaling: 1/10

INTEGER_16