7 fault reaction active, Fault reaction active, 7cia402 device profile – Lenze i700 User Manual

Page 187

Advertising
background image

Lenze · i700 servo inverter · Reference manual · DMS 1.5 EN · 03/2014 · TD05

187

7

CiA402 device profile

7.4

Device control

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

7.4.2.7

Fault reaction active

If a minor fault occurs, i. e. the drive is still able

to actuate the motor in a controlled manner,

this device status becomes active and the drive

is brought to a standstill irrespective of the

setpoint specified with the deceleration set for

quick stop (

0x6085

or

0x6885

for axis B).

• Only the parameters of the inverter can be

changed which do not require controller

inhibit.

• The motor brake, if available, is opened.
• The drive control is working.

Bit pattern for the "Fault reaction active" device status in the Statusword (

0x6041

or

0x6841

for axis B):

Bits 15 - 8

Bit 7

Bit 6

Bit 5

Bit 4

Bit 3

Bit 2

Bit 1

Bit 0

Warning is

active

Switch on

disabled

Quick stop

Voltage

enabled

Fault active

Operation

enabled

Switched on

Ready to

switch on

X

X

0

X

X

1

1

1

1

Note!

After quick stop has been executed, i. e. when the drive is at standstill, an automatic

changeover to the "

Fault

" device status is effected.

The "

Fault

" device status can only be exited using the "

Fault reset

" command if the cause

of the fault is eliminated.

Ready to

switch on

Not ready to

switch on

Switched

on

Operation

enabled

Fault reaction

active

Fault

active

Switch on

disabled

Quick stop

active

Power on