Defining the behaviour at the current, Limit (imax controller), 5motor control & motor settings – Lenze i700 User Manual

Page 143

Advertising
background image

Lenze · i700 servo inverter · Reference manual · DMS 1.5 EN · 03/2014 · TD05

143

5

Motor control & motor settings

5.14

Parameterising the V/f characteristic control

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

5.14.5

Defining the behaviour at the current limit (Imax controller)

The maximum output current or the current limit is determined by the object "Max. current"

(

0x6073

or

0x6873

for axis B). In case of the V/f characteristic control, an lmax controller is

implemented for complying with this limit. If the motor current exceeds the set maximum value,

the lmax controller is activated.

• The Imax controller changes the field frequency so that the motor current does not exceed the

current limit. In motor mode, the frequency is reduced and in generator mode it is increased.

• The gain and reset time of the Imax controller can be parameterised.

• For the automatic calculation of these two parameters, the "VFC: Calculate Imax controller

parameters" function is provided via object

0x2822

(or

0x3022

for axis B).

Optimising the Imax controller
The automatic calculation serves to determine starting parameters of the Imax controller which are

sufficient for many applications. Thus, an optimisation is not required for most of the applications.
The parameters of the Imax controller have to be adapted if

• a power control is implemented with great moments of inertia.

Recommendation:
Step 1: Increase reset time in

0x2B08:2

(or

0x3308:2

for axis B)

Step 2: Reduce gain in

0x2B08:1

(or

0x3308:1

for axis B)

• vibrations occur with V/f characteristic control during the operation of the Imax controller.

Recommendation:
Step 1: Increase reset time in

0x2B08:2

(or

0x3308:2

for axis B)

Step 2: Reduce gain in

0x2B08:1

(or

0x3308:1

for axis B)

• overcurrent errors occur due to load impulses or too high acceleration/deceleration ramps.

Recommendation:
Step 1: Reduce reset time in

0x2B08:2

(or

0x3308:2

for axis B)

Step 2: Increase gain in

0x2B08:1

(or

0x3308:1

for axis B)

Subindex 2:

VFC: Load adjustment - value

Load adjustment in [%] proportionally to the rated torque, in order to obtain a correspondingly "rigid" drive

behaviour even after the starting action.

• When starting torque = rated torque, a load adjustment of 50 % is suitable for most applications.

Setting range

(min. value | unit | max. value)

Lenze setting

0.00

%

200.00 20.00 %

Write access  CINH  OSC  P  RX  TX

Scaling: 1/100

UNSIGNED_32