8

Monitoring functions

8.5

Motor temperature monitoring

250

Lenze · i700 servo inverter · Reference manual · DMS 1.5 EN · 03/2014 · TD05

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

8.5

Motor temperature monitoring

0x2D49 | 0x3549 - Motor temperature monitoring: Parameters

Sub.

Name

Lenze setting

Data type

1

Motor temperature monitoring: Sensor type

0: KTY83-110

UNSIGNED_8

2

Motor temperature monitoring: Response

1: Trouble

UNSIGNED_8

3

Motor temperature monitoring: Warning

threshold

145.0 °C

INTEGER_16

4

Motor temperature monitoring: Error

threshold

155.0 °C

INTEGER_16

5

Motor temperature monitoring: Actual motor

temperature

INTEGER_16

6

Thermal sensor characteristic: Grid point 1 -

temperature

25.0 °C

INTEGER_16

7

Thermal sensor characteristic: Grid point 2 -

temperature

150.0 °C

INTEGER_16

8

Spec. charact.: resistance sampling point 1

1000 Ohm

INTEGER_16

9

Spec. charact.: resistance sampling point 2

2225 Ohm

INTEGER_16

Subindex 1:

Motor temperature monitoring: Sensor type

Selection of the motor temperature sensor used
Selection list

(Lenze setting printed in bold)

Info

0 KTY83-110
1 KTY83-110 + 2 x PTC 150 °C (series connection)
2 KTY84-130
3 Spec. charact. curve

From version 01.03

Spec. charact. curve for motor temperature sensor

Write access  CINH  OSC  P  RX  TX

UNSIGNED_8

Subindex 2:

Motor temperature monitoring: Response

Response when tripping the motor temperature monitoring

• In order to exclude an unwanted tripping of the fault during initial commissioning without connected motor, the

error response is a warning as long as the device is in the "switch-on inhibited" status. If this status is left, the

error response parameterised here is triggered.

Selection list

(Lenze setting printed in bold)

0 No response
1 Fault

Write access  CINH  OSC  P  RX  TX

UNSIGNED_8

Subindex 3:

Motor temperature monitoring: Warning threshold

Warning threshold for motor temperature monitoring

• Reset is effected with a hysteresis of 5 °C.

Setting range

(min. value | unit | max. value)

Lenze setting

-3276.8

°C

3276.7 145.0 °C

Write access  CINH  OSC  P  RX  TX

Scaling: 1/10

INTEGER_16

Subindex 4:

Motor temperature monitoring: Error threshold

Error threshold for motor temperature monitoring

• Reset is effected with a hysteresis of 5 °C.

Setting range

(min. value | unit | max. value)

Lenze setting