CiA402 error codes / error messages

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

Error code 0xFF0D: No resolver connected --> command cannot be executed.

Text ID: 0x31

Error code 0xFF0E: Speed too low --> command cannot be executed.

Text ID: 0x32

Error code 0xFF0F: No resolver connected --> command cannot be executed.

Text ID: 0x33

Error code 0xFF10: Time-out

Text ID: 0x34

Error code 0xFF11: Numerical problem

Text ID: 0x35

Error code 0xFF12: Inverter error too big

Text ID: 0x36

Cause

Remedies

Response

The identification of a resolver error

was attempted during V/f

characteristic control without

feedback system.

The resolver error can only be

identified if the resolver is used as

feedback system during servo

control.

Warning

Cause

Remedies

Response

The actual speed is too low for the

resolver error to be identified.

Repeat identification at higher

speed.

Warning

Cause

Remedies

Response

The identification of a resolver error

was attempted but an encoder is

used as feedback system.

Identification is only possible with

devices with resolver feedback.

Warning

Cause

Remedies

Response

The actual speed is too low for the

resolver error to be identified.

Repeat identification at higher

speed.

Warning

Cause

Remedies

Response

The actual speed is too low for the

resolver error to be identified.

Repeat identification at higher

speed.

Warning

Cause

Remedies

Response

The results of the inverter error

identification are not plausible.

Check shielding of the motor cable.

Connect the shield with a surface as

large as possible.

Warning