0x2ba5 | 0x33a5 - flying restart: delay time, 0x2ba6 | 0x33a6 - flying restart: result, 0x2ba5 – Lenze i700 User Manual

Page 152: 0x33a5, 0x2ba6, 0x33a6, 5motor control & motor settings

Advertising
background image

5

Motor control & motor settings

5.14

Parameterising the V/f characteristic control

152

Lenze · i700 servo inverter · Reference manual · DMS 1.5 EN · 03/2014 · TD05

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

0x2BA5 | 0x33A5 - Flying restart: Delay time

0x2BA6 | 0x33A6 - Flying restart: Result

To avoid starting a flying restart process at short-time controller inhibit, a time can be set here for the minimum

active controller inhibit time before a flying restart process is activated.

• Since a pulse inhibit > 500 ms causes a controller inhibit, this also applies to the pulse inhibit.

Setting range

(min. value | unit | max. value)

Lenze setting

0

ms

10000 0 ms

Write access  CINH  OSC  P  RX  TX

UNSIGNED_16

Output of the speed found for acceptance in the control.

• This information is pending until the control reports acceptance of the found speed to the i700 servo inverter via

bit 0 in the Lenze control word (

0x2830

or

0x3030

for axis B).

Sub.

Name

Lenze setting

Data type

1

Flying restart: Determined speed [rpm]

INTEGER_16

2

Flying restart: Determined speed [n unit]

INTEGER_32

Subindex 1:

Flying restart: Determined speed [rpm]

Display area

(min. value | unit | max. value)

Initialisation

-32768

r/min

32767

Write access  CINH  OSC  P  RX  TX

INTEGER_16

Subindex 2:

Flying restart: Determined speed [n unit]

Display area

(min. value | unit | max. value)

Initialisation

-480000

[n unit]

480000

Write access  CINH  OSC  P  RX  TX

Scaling: 480000/2

31

INTEGER_32