Asynchronous motor (asm): identifying the lh, Saturation characteristic, 5motor control & motor settings – Lenze i700 User Manual

Page 129

Advertising
background image

Lenze · i700 servo inverter · Reference manual · DMS 1.5 EN · 03/2014 · TD05

129

5

Motor control & motor settings

5.12

Fine adjustment des motor model

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

5.12.3

Asynchronous motor (ASM): Identifying the Lh saturation characteristic

In case of an asynchronous motor, the relationship between current and torque is basically

determined by the saturation behaviour of the mutual inductance. If the achieved torque accuracy,

especially in the field weakening range should not be sufficient, the accuracy can be increased by

the individual identification of the saturation characteristic. This behaviour can be measured by the

i700 servo inverter.

Preconditions for the execution

• Before this commissioning function is executed, the inverter characteristic and the motor

parameters have to be identified.

Compensating for inverter influence on output voltage

( 71)

Determine motor parameters automatically via "motor parameter identification"

( 78)

• The motor may be firmly braked.
• The controller is free of errors and is in the "

Switched on

" device status.

Response of the motor during the execution
Standstill

How to identify the LH saturation characteristic:

1. If the controller is enabled, inhibit the controller.

Enable/inhibit operation via control word

( 59)

2. Set object

0x2825

(or

0x3025

for axis B) to "10" to change to the "Determine Lh saturation

characteristicn" operating mode.

3. Enable the controller to start the procedure.

Notes:

• The identification of the Lh saturation characteristic can take up to 11 minutes. The

progress can be checked in the object

0x2823

(or

0x3023

for axis B).

• By means of controller inhibit, the started procedure can be cancelled any time, if

required. Characteristic values that have already been determined are rejected in this

case.

After successful completion...
...the controller will be inhibited automatically and the points of the determined LH characteristic

will be set in object

0x2C07

(or

0x3407

for axis B).

• For permanent storage, the changed settings must be uploaded to the controller from the i700

servo inverter.
The »EASY Starter« serves to save the parameter settings of the i700 servo inverter as parameter

file (*.gdc). In the »PLC Designer«, this file can then be imported in the corresponding axis.

Saving changed parameters safe against mains failure

( 60)

• The controller inhibit automatically set by the procedure can be deactivated via the

Controlword (

0x6040

or

0x6840

for axis B) (setting = 7, 15).

In the event of an error
If an error occurs during the procedure or the pulse inhibit gets active (e.g. due to short-time

undervoltage), the procedure is terminated with controller inhibit without a change in settings.