Motor control & motor settings

5.3

Wiring check by means of manual test modes

64

Lenze · i700 servo inverter · Reference manual · DMS 1.5 EN · 03/2014 · TD05

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

Preconditions for the execution

• The motor must be able to rotate freely.
• The controller is free of errors and is in the "

Switched on

" device status.

Response of the motor during the execution
The motor rotates as a function of the set output frequency.

How to activate the manual test mode "current/frequency":

1. If the controller is enabled, inhibit the controller.

Enable/inhibit operation via control word

( 59)

2. Set object

0x2825

(or

0x3025

for axis B) to "2" to change to the "Current/frequency" test

mode.

3. Enable the controller to start the test mode.
4. To stop the test mode:

• Inhibit controller.
• Set object

0x2825

(or

0x3025

for axis B) to "0" to change back to the CiA402 mode.

Stop!

In the case of the synchronous motor, a jerky compensating movement occurs after

controller enable if the pole position of this movement does not correspond to the

starting angle.