Motor control & motor settings

5.14

Parameterising the V/f characteristic control

150

Lenze · i700 servo inverter · Reference manual · DMS 1.5 EN · 03/2014 · TD05

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

Flying restart process
If the "flying restart process" function is activated, the flying restart process will start after controller

enable:

1. The i700 servo inverter reports the started flying restart process to the controller via bit 8 in the

Lenze status word (

0x2831

or

0x3031

for axis B).

2. If a speed has been found, it is reported to the controller via bit 9 in the Lenze-status word.
3. The controller gives the i700 servo inverter a feedback on the fact that the found speed has been

accepted via bit 0 in the Lenze control word (

0x2830

or

0x3030

for axis B). As long as the

feedback is not provided, further flying restart processes are not possible.

[5-12] Signals during a flying restart process

Parameter setting

A control loop is involved in the flying restart process the controller parameter integration time of

which has to be adapted to the motor in the object

0x2BA3

(or

0x33A3

for axis B). For the automatic

calculation of this parameter, the "VFC: Flying restart process controller - calculate controller

parameters" function is available via the object

0x2822

(or

0x3022

for axis B).

0x2BA6 | 0x33A6

0x2831 | 0x3031

0x2831 | 0x3031

0x2830 | 0x3030

Bit 0: Flying restart acknowledge

Search...

OperationEnabled

Bit 8: Flying restart running

Bit 9: Flying restart ready

Found velocity

Note!

• The flying restart algorithm requires the motor voltage as exact as possible. Therefore

it is absolutely necessary to predetermine the inverter error characteristic.

Compensating for inverter influence on output voltage

• In addition to the exact motor voltage, the exact stator resistance must also be

known. If the flying restart process does not work as desired, the setting of the stator

resistance is to be slightly adapted in object

0x2C01:2

(or

0x3401:2

for axis B).

• A flying restart process can be blocked via bit 1 in the Lenze control word (

0x2830

or

0x3030

for axis B).