The i700 servo inverter features three different EtherCAT monitoring modes:

• Sync0 monitoring when DC mode is used
• PDO frame failure detection when DC mode is used
• Monitoring to EtherCAT line interruption

Sync0 monitoring when DC mode is used
This monitoring mode checks whether the Sync0 Signals are generated at the correct time in the

i700 servo inverter if the "Distributed Clock mode" (DC mode) has been selected and the i700 servo

inverter is in the "Operational" status.

• If no Sync0 signals arrive anymore during double the Sync0 cycle time, the i700 servo inverter

changes to the "Safe-Operational" status and triggers an error (CiA402 error code 0x8700). 0x32

is returned as bus status (AL status code).

• After "Pre-Operational" has changed to "Safe-Operational", the generation of Sync0 pulses has

to be started within 5 seconds. If this is not the case, or if a change from "Safe-Operational" to

"Operational" is requested without the signals being generated accordingly, this error is

triggered as well.

• This monitoring mode cannot be configured.

PDO frame failure detection when DC mode is used
This monitoring mode checks whether an EtherCAT-PDO telegram (Sync Manager 2 Event) has

arrived between two Sync0 signals if the "Distributed Clock mode" (DC mode) has been selected. For

this purpose, the i700 servo inverter is provided with an internal frame failure error counter which

is increased by the value "3" in case of a frame failure. For every PDO received correctly, the error

counter is reduced by the value "1".
This monitoring mode can be configured via the

0x10F1:2

object:

From version 01.04

, monitoring is activated in the Lenze setting (

0x10F1:2

= "20").

• If a value higher than "0" is set in

0x10F1:2

: If the internal frame failure error counter reaches

the set value, the i700 servo inverter changes to the "Safe-Operational" status and triggers an

error (CiA402 error code 0x8700).

Object

Name

Data type

0x10F1

ECAT: Behaviour in case of error

RECORD

0x2000

Device: Data

RECORD

0x2001

Device: Name

STRING(128)

0x2021

Device: Optical recognition

RECORD

0x2022

Device command

UNSIGNED_32

0x2540

Device: Voltage values

RECORD

0x2580

ECAT DC: Real-time information