Error code 0x2386: clamp is active, Error code 0x2387: clamp responded too often, 9diagnostics & error management – Lenze i700 User Manual

Page 269

Advertising
background image

Lenze · i700 servo inverter · Reference manual · DMS 1.5 EN · 03/2014 · TD05

269

9

Diagnostics & error management

9.4

CiA402 error codes / error messages

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

Error code 0x2386: Clamp is active

Text ID: 0x2F

Error code 0x2387: Clamp responded too often

Text ID: 0x30

Error code 0x3210: DC link circuit - overvoltage [value] V

Text ID: 0x0A

Delay time: 5 ms

Error code 0x3220: DC link circuit - undervoltage [value] V

Text ID: 0x0B

Error code 0x4210: Module temperature too high, [value]

Text ID: 0x0C

Monitoring of the heatsink temperature

Cause

Remedies

Response

Maximum current of the axis (display

in

0x2DDF:2

|

0x35DF:2

) has been

reached.

• Select a flatter speed ramp.

• Reduce the load.

• Set the Imax controller

(

0x2B08

|

0x3308

) more

dynamically.

Warning

Cause

Remedies

Response

Maximum current of the axis (display

in

0x2DDF:2

|

0x35DF:2

) was

reached too often in a row.

• Select a flatter speed ramp.

• Reduce the load.

• Set the Imax controller

(

0x2B08

|

0x3308

) more

dynamically.

Fault

Cause

Remedies

Response

Due to a too high braking energy, the

DC-bus voltage exceeds the

overvoltage threshold which results

from the mains voltage setting.

• Connect brake resistor to power

supply module or use

regenerative module.

• Check mains setting.

• Check drive profile.

Warning or fault

(depending on the height of the

voltage)

• Warning threshold adaptable in

0x2540:5

.

• Fixed error threshold.

Cause

Remedies

Response

DC bus voltage is lower than the

undervoltage threshold resulting

from the mains setting.

• Check mains voltage.

• Check DC-bus voltage.

• Check mains settings.

Warning or fault

(depending on the height of the

voltage)

• Warning threshold adaptable in

0x2540:2

.

• Fixed error threshold.

Cause

Remedies

Response

Heatsink temperature higher than

fixed temperature limit (100 °C):

• Ambient controller temperature

too high.

• Dirty fan or ventilation slots.

• Fan defective.

• Warning threshold set too low.

• Check control cabinet

temperature.

• Clean filter.

• Clean controller.

• Replace fan.

Warning or fault

(depending on the height of the

temperature)

• Warning threshold can be

adapted in

0x2D84:2

|

0x3584:2

.

• Fixed error threshold.