CiA402 device profile

7.4

Device control

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

7.4.3

Selection of the operating mode

The drive behaviour depends on the selected operating mode. The operating mode is selected by the

Controller via the

0x6060

object (or

0x6860

for axis B) in the communication statuses "Pre-

Operational" or "Operational". Access can be effected via SDO or PDO.

• Only one operating mode at a time can be active.
• The operating modes differ by the type of setpoint selection.
• The following table shows the permissible operating modes with the corresponding object

value:

Tip!
The operating mode currently set can be read via the

0x6061

object (or

0x6861

for axis B).

For this object, too, access is possible via SDO or PDO.

Modes of operation

Object value

Setpoint selection

Velocity mode (vl)

2

Velocity

Cyclic sync position mode (csp)

8

Position

Cyclic sync velocity mode (csv)

9

Velocity

Cyclic sync torque mode (cst)

10

Torque

-

All other values

- (Standstill)