1 supported drive modes, Supported drive modes, 7cia402 device profile – Lenze i700 User Manual

Page 165

Advertising
background image

Lenze · i700 servo inverter · Reference manual · DMS 1.5 EN · 03/2014 · TD05

165

7

CiA402 device profile

7.1

Supported drive modes

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

7.1

Supported drive modes

Setpoint interpolation in the operating modes with a cyclic setpoint selection
When an operating mode with cyclic setpoint selection is selected, first all setpoints are controlled

via interpolators, which divide the setpoint step-changes down from the bus cycle to the cycle time

of the control loops. All interpolators are parameterised commonly via the "Interpolation time

period" object (

0x60C2

or

0x68C2

for axis B).

7.2

Applied units and scaling for position and velocity

CiA402 - drive modes

Can be used with

Servo control

V/f characteristic

control

Velocity mode (vl)

• Speed control

Cyclic sync velocity mode (csv)

• Speed control with interpolation of the speed setpoint.

Cyclic sync torque mode (cst)

• Torque control with interpolation of the torque setpoint.

Cyclic sync position mode (csp)

• Position control with interpolation of the position setpoint.

Name

Unit

Scaling

CiA402 position

Pos unit

2

16

... 2

30

[Pos unit] ≡ 360°

Depending on the position encoder resolution set (

0x608F

or

0x688F

for axis B).

Internal position

Incr.

2

32

[Incr.] ≡ 360°

CiA402 velocity

r/min

Internal velocity

n-unit

±2

31

[n-unit] ≡ ±480000 r/min