2 resetting the error/fault, 0x2840 | 0x3040 - delay time: reset error, 0x2841 | 0x3041 - reset error – Lenze i700 User Manual

Page 264: Resetting the error/fault, 0x2840, 0x3040, 0x2826, 0x3026, 0x2841, 0x3041

Advertising
background image

9

Diagnostics & error management

9.2

Indication of fault and warning (error code)

264

Lenze · i700 servo inverter · Reference manual · DMS 1.5 EN · 03/2014 · TD05

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

0x2826 | 0x3026 - Quick stop: Duration in the event of a fault

9.2.2

Resetting the error/fault

• A fault can only be reset via bit 7 in the Controlword (

0x6040

or

0x6840

for axis B).

• If there is another fault pending after resetting the fault, bit 3 in the status word remains set

and object

0x603F

(or

0x683F

for axis B) now shows the error code of this fault.

• Certain errors can only be reset by 24 V mains switching. These are, for instance, internal errors

due to internal communication faults, initialisation errors, and checksum errors of the firmware

or the persistent data (elapsed-hour meters and power-on hour meters, calibration values, etc.).

• Certain errors (e.g. earth fault or short circuit of the motor phases) can cause a delay time. In this

case, the fault can only be reset via bit 7 in the Controlword after the delay time has elapsed.

• Active delay times are displayed via bit 14 in the Lenze status word (

0x2831

or

0x3031

for axis

B).

• The remaining delay time can be read out via the following object:

0x2840 | 0x3040 - Delay time: Reset error

0x2841 | 0x3041 - Reset error

In parallel to the execution of a quick stop in the "Fault reaction active" device status, this timer is started.

Depending on which of the following two conditions occurs first, the device status changes from "Fault reaction

active" to "Fault":

• Condition 1: Quick stop has braked the drive to standstill.

• Condition 2: This timer has elapsed.

The status change to "Fault" triggers a pulse inhibit and, if available, the holding brake is applied.

Note!

In case of setting "-2: Quick stop if possible..." in

0x605E

(or

0x685E

for axis B):

If due to an encoder error, quick stop is replaced by DC current braking or short-circuit braking, a standstill cannot

be detected anymore. In this case, only the condition 2 (timer has elapsed) causes an exit of the "Fault reaction

active" device status.

Setting range

(min. value | unit | max. value)

Lenze setting

0

s

100 4 s

Write access  CINH  OSC  P  RX  TX

UNSIGNED_32

Display area

(min. value | unit | max. value)

Initialisation

-2147483648

ms

2147483647 0 ms

Write access  CINH  OSC  P  RX  TX

INTEGER_32

Setting range

(min. value | unit | max. value)

Lenze setting

0

1 0

Write access  CINH  OSC  P  RX  TX

UNSIGNED_8