Error code 0x8282: sync manager - settings [value, Error code 0x8286: pdo mapping - error, 9diagnostics & error management – Lenze i700 User Manual

Page 273

Advertising
background image

Lenze · i700 servo inverter · Reference manual · DMS 1.5 EN · 03/2014 · TD05

273

9

Diagnostics & error management

9.4

CiA402 error codes / error messages

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

Error code 0x8281: Sync Manager - actual size [value]

Text ID: 0x17

Error code 0x8282: Sync Manager - settings [value]

Text ID: 0x18

Error code 0x8283: PDO Mapping: Object unknown (index [value])

Text ID: 0x2B

Error code 0x8284: No PDO mapping object (index [value])

Text ID: 0x2C

Error code 0x8285: Too many mapped objects (max. number = [value])

Text ID: 0x2D

Error code 0x8286: PDO mapping - error

Text ID: 0x2E

Cause

Remedies

Response

Incorrect Sync Manager setting of the

EtherCAT master.

• Check the devices on the bus.

• Check cabling or sequence of the

devices on the bus.

• Remove the i700 servo inverter

from the project tree and rescan

the bus.

• Check the device description of

the i700 servo inverter.

Fault

Cause

Remedies

Response

Incorrect Sync Manager setting of the

EtherCAT master.

• Check the devices on the bus.

• Check cabling or sequence of the

devices on the bus.

• Remove the i700 servo inverter

from the project tree and rescan

the bus.

• Check the device description of

the i700 servo inverter.

Fault

Cause

Remedies

Response

Unknown index in the PDO mapping. Check PDO mapping.

Fault

Cause

Remedies

Response

Index cannot be mapped as PDO.

Check PDO mapping.

Fault

Cause

Remedies

Response

Max. number of PDO mapping

objects has been exceeded (> 64).

Reduce the number of mapping

objects in the "free mapping".

Fault

Cause

Remedies

Response

Incorrect PDO mapping.

Check PDO mapping.

Fault