145

5

Motor control & motor settings

5.14

Parameterising the V/f characteristic control

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

5.14.6

Setting the slip compensation

The slip compensation serves to automatically compensate a load-dependent speed loss. In order

that the slip compensation can operate correctly, the rated slip of the motor is required. It is

calculated from the rated motor frequency and the rated motor speed, thus both parameters must

be parameterised correctly.

0x2B09 | 0x3309 - VFC: Slip compensation - Parameter

Sub.

Name

Lenze setting

Data type

1

VFC: Slip compensation - influence

0.00 %

INTEGER_16

2

VFC: Slip compensation - filter time

2000 ms

UNSIGNED_16

Subindex 1:

VFC: Slip compensation - influence

Adjustment in percent of the slip calculated

• For instance required for deviations of the real motor data from the nameplate data.

• A setting of 100 % corresponds to the rated slip of the machine.

Setting range

(min. value | unit | max. value)

Lenze setting

-200.00

%

200.00 0.00 %

Write access  CINH  OSC  P  RX  TX

Scaling: 1/100

INTEGER_16

Subindex 2:

VFC: Slip compensation - filter time

Adjustment of the time-dependent behaviour of the slip compensation
Setting range

(min. value | unit | max. value)

Lenze setting

1

ms

6000 2000 ms

Write access  CINH  OSC  P  RX  TX

UNSIGNED_16