Monitoring functions

8.4

Monitoring of the motor utilisation (I²xt)

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

Speed-dependent evaluation of the motor current
By selecting a characteristic, the permissible motor current is evaluated depending on speed for

calculating the thermal motor utilisation. For this purpose, up to four operating points on the S1

characteristic of a motor can be used.

• The S1 characteristic can be found in the technical data sheet/catalogue of the respective

motor.

• The representation in the objects /characteristic is carried out as relative values with reference

to rated values.

0x2D4D | 0x354D - Motor utilisation (I²xt): User-definable characteristic

An example of how to enter the characteristic can be found in the following subchapter.

Note!

When you select a Lenze motor from the catalogue and transfer its parameters into the

controller, a typical characteristic is automatically set for the selected motor. A deviating

parameterisation is only required if the motor is operated in ambient conditions which

demand a general derating. Example: Use in site altitudes > 1000 m.
In case of motors of other manufacturers, the operating points have to be parameterised

based on the data sheet information.

Operating points

Standstill n01-I01

For motors, this operating point is often described with

the no-Io values.

Reference point n02-I02

If the value falls below the speed n02, a derating in the

current is required because:

• the motor cooling of self-ventilated motors

deteriorates considerably.

• a DC current load causes an increased power loss in a

winding.

For motors, this operating point is also described with

the no*-Io* values.

Rated point (n03=nrated)-(I03=Irated)

Rated values of the motor are the reference for all

operating points of the i²xt monitoring.

Field weakening n04-I04

This operating point should be parameterised

independently of the use in the current application.

Sub.

Name

Lenze setting

Data type

1 I²xt: x1 = n01/nN (n01 ~ 0)

0 %

UNSIGNED_16

2 I²xt: y1 = i01/iN (x = n01 ~ 0)

100 %

UNSIGNED_16

3 I²xt: x2 = n02/nN (n02 = limit - reduced cooling) 0 %

UNSIGNED_16

4 I²xt: y2 = i02/iN (x = n02 = limit - reduced

cooling)

100 %

UNSIGNED_16

5 I²xt: x3 = n03/nN (n03 = rated speed)

100 %

UNSIGNED_16

6 I²xt: y3 = i03/iN (x = n03 = rated speed)

100 %

UNSIGNED_16

7 I²xt: x4 = n04/nN (n04 = limit - field weakening) 100 %

UNSIGNED_16

8 I²xt: y4 = i04/iN (x = n04 = limit - field

weakening)

100 %

UNSIGNED_16

Write access  CINH  OSC  P  RX  TX