5

Motor control & motor settings

5.14

Parameterising the V/f characteristic control

144

Lenze · i700 servo inverter · Reference manual · DMS 1.5 EN · 03/2014 · TD05

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

If the connected mechanics and the conditions in the machine allow it, it may be helpful to

determine the optimal parameters of the current controller by a practical acceleration test with a

reduced maximum current (

0x6073

or

0x6873

for axis B). Mass inertia and

acceleration/deceleration considerably determine the requirements of the Imax control loop.

Recommendation: Execute the adjustment with the real mass inertia and optimise the

parameters step by step with an increasing acceleration/deceleration. The oscilloscope function

of the »PLC Designers«/»EASY motor starter« serves to record the following objects:

• VFC: Setpoint frequency (

0x2B0B

or

0x330B

for axis B)

• Motor: Actual voltage (

0x2D82

or

0x3582

for axis B)

• Motor: Actual current (

0x2DD1:5

or

0x35D1:5

for axis B)

• Device: Max. current (

0x6073

or

0x6873

for axis B)

• Device: Actual output frequency (

0x2DDD

or

0x35DD

for axis B)

0x2B08 | 0x3308 - VFC: Imax controller - Parameter

Sub.

Name

Lenze setting

Data type

1

VFC: Imax controller - gain

0.001 Hz/A

UNSIGNED_32

2

VFC: Imax controller - reset time

100.0 ms

UNSIGNED_32

Subindex 1:

VFC: Imax controller - gain

Gain for Imax controller
Setting range

(min. value | unit | max. value)

Lenze setting

0.000

Hz/A

1000.000 0.001 Hz/A

Write access  CINH  OSC  P  RX  TX

Scaling: 1/1000

UNSIGNED_32

Subindex 2:

VFC: Imax controller - reset time

Reset time for Imax controller
Setting range

(min. value | unit | max. value)

Lenze setting

1.0

ms

2000.0 100.0 ms

Write access  CINH  OSC  P  RX  TX

Scaling: 1/10

UNSIGNED_32