8.7

Motor phase failure monitoring

254

Lenze · i700 servo inverter · Reference manual · DMS 1.5 EN · 03/2014 · TD05

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

8.7

Motor phase failure monitoring

0x2D45 | 0x3545 - Motor phase failure detection

Note!

In the Lenze setting, the monitoring function is not activated!

Sub.

Name

Lenze setting

Data type

1

Motor phase failure 1: Response

0: No Response

UNSIGNED_8

2

Motor phase failure 1: Current threshold

5.0 %

UNSIGNED_8

3

Motor phase failure 1: Voltage threshold

10.0 V

UNSIGNED_16

4

Motor phase failure 2: Response

0: No Response

UNSIGNED_8

Subindex 1:

Motor phase failure 1: Response

Monitoring 1 (in the "operation enabled" status):

Response during activation

Selection list

(Lenze setting printed in bold)

0 No response
1 Fault
2 Warning

Write access  CINH  OSC  P  RX  TX

UNSIGNED_8

Subindex 2:

Motor phase failure 1: Current threshold

Monitoring 1 (in the "operation enabled" status):

Selection of the current threshold for activation

• 100 % ≡ maximum axis current (

0x2DDF:2

or

0x35DF:2

for axis B)

• Background: In order to be able to reliably detect the failure of a motor phase, a certain motor current for the

current sensors must flow first. The monitoring function therefore is only activated if, in the case of a servo

control, the setpoint of the motor current, and in the case of a V/f characteristic control, the actual value of the

motor current (display in

0x6078

or

0x6878

for axis B) has exceeded the current threshold set here.

Setting range

(min. value | unit | max. value)

Lenze setting

1.0

%

10.0 5.0 %

Write access  CINH  OSC  P  RX  TX

Scaling: 1/10

UNSIGNED_8

Subindex 3:

Motor phase failure 1: Voltage threshold

Monitoring 1 (in the "operation enabled" status):

Selection of the voltage threshold for monitoring several motor

phases

• The V/f characteristic control enables the detection of several failed motor phases during operation.

• Monitoring with regard to a failure of several motor phases is active if

• a response other than "0: No response" is set in subindex 1, and

• the motor voltage exceeds the voltage threshold set here.

• The "Motor disconnected" error message is output if the motor current is lower than the device-dependent

threshold value for more than 20 ms.

• The monitoring function for the failure of several motor phases can be deactivated if the value "1000.0 V" is set

here.

Setting range

(min. value | unit | max. value)

Lenze setting

0.0

V

100.0 10.0 V

Write access  CINH  OSC  P  RX  TX

Scaling: 1/10

UNSIGNED_16