Lenze · i700 servo inverter · Reference manual · DMS 1.5 EN · 03/2014 · TD05

147

5

Motor control & motor settings

5.14

Parameterising the V/f characteristic control

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

Parameter setting
The gain of the oscillation signal is to be set according to the following equation:

The time constant of the PT1 filter has to be set in such a way that the oscillation can be damped

and higher-frequency components are filtered out of the signal. The time constant is determined

from the reciprocal value of the double frequency of the current oscillation.

The oscillation frequency calculated can be limited before it is added to the field frequency. The

maximum frequency can be derived from the amplitude of the current oscillation, the rated motor

current, and the slip frequency of the connected motor:

0x2B0A | 0x330A - VFC: Oscillation damping - Parameter

Gain of the oscillation signal

Current amplitude

2 Maximum device current

-----------------------------------------------------------------------------

100 %

=

Time constant

1

2 Oscillation frequency

--------------------------------------------------------------

=

Max. frequency

2 Amplitude of the current oscillation

Rated motor current

----------------------------------------------------------------------------------------------------

Rated slip frequency

=

Sub.

Name

Lenze setting

Data type

1

VFC: Oscillation damping - gain

20 %

INTEGER_16

2

VFC: Oscillation damping - filter time

5 ms

UNSIGNED_16

3

VFC: Oscillation damping - limitation

0.2 Hz

UNSIGNED_16

4

VFC: Oscillation damping - ramp-end

frequency

0 %

UNSIGNED_8

Subindex 1:

VFC: Oscillation damping - gain

Gain of the oscillation signal

• If the setting is "0 %", the oscillation damping is switched off.

Setting range

(min. value | unit | max. value)

Lenze setting

-100

%

100 20 %

Write access  CINH  OSC  P  RX  TX

INTEGER_16

Subindex 2:

VFC: Oscillation damping - filter time

Time constant of the PT1 filter
Setting range

(min. value | unit | max. value)

Lenze setting

1

ms

600 5 ms

Write access  CINH  OSC  P  RX  TX

UNSIGNED_16

Subindex 3:

VFC: Oscillation damping - limitation

Limitation of the calculated oscillation frequency before it is added to the field frequency.
Setting range

(min. value | unit | max. value)

Lenze setting

0.1

Hz

20.0 0.2 Hz

Write access  CINH  OSC  P  RX  TX

Scaling: 1/10

UNSIGNED_16