0x2831 | 0x3031 - lenze status word, 0x2831, 0x3031 – Lenze i700 User Manual

Page 29: 3communication with the controller

Advertising
background image

Lenze · i700 servo inverter · Reference manual · DMS 1.5 EN · 03/2014 · TD05

29

3

Communication with the controller

3.5

Lenze control and status word

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

0x2831 | 0x3031 - Lenze status word

In the Lenze status word, messages are combined that go beyond the CiA specification.

Display area

(min. value | unit | max. value)

Initialisation

0x0000

0xFFFF

Value is bit-coded:

Info

Bit 0 Position controller: In limitation

Position mode: Output of the position controller in

limitation

Bit 1 Speed: Limited speed setpoint 1

Input of speed controller 1 in limitation

Bit 2 Speed controller: In limitation

Output of speed controller 1 in limitation

Bit 3 Torque: Limited target torque

Target torque in limitation

Bit 4 Motor: Limited current setpoint

Setpoint current in limitation

Bit 5 Speed: Limited speed setpoint 2

Torque mode: Input of speed controller 2 in limitation

Bit 6 Upper speed limit is active

Torque mode: Speed is limited to the upper speed limit

(

0x2946:1

or

0x3146:1

for axis B)

Bit 7 Lower speed limit is active

Torque mode: Speed is limited to the lower speed limit

(

0x2946:2

or

0x3146:2

for axis B)

Bit 8 Flying restart in progress ...

V/f operation: "Flying restart process" function is active

Bit 9 Flying restart: Ready for operation

V/f operation: "Flying restart process" function has

acquired speed

Bit 10 Limited output frequency

V/f operation: Setpoint frequency in limitation

Bit 11 Asynchronous motor magnetised

In case of servo control for synchronous motor (SM):

• Bit is always set.

In case of servo control for asynchronous motor (ASM):

• Bit is set if the difference between setpoint and actual

flux is smaller than 10 % of setpoint flux.

• Bit is reset if the difference has increased to 15 % of

setpoint flux.

In case of V/f operation:

• Bit is set if the rotor time constant has been passed

seven times, calculated from the time the controller

has been enabled and no restart on the fly has been

active and the total motor current has reached 20 %

of the rated motor current for the first time.

Otherwise 0.

Bit 12 Motor phase failure detection in

progress ...

Motor phase failure detection is active

Bit 13 Feedback: Open circuit

Position feedback is interrupted

Bit 14 Delay time: 'Reset error' is active

The error cannot be reset before the delay time has

expired. The remaining delay time is displayed in

0x2840

(or

0x3040

for axis B).

Bit 15 Clamp is active

V/f operation: Clamp (short-time inhibit of the inverter)

is active

Write access  CINH  OSC  P  RX  TX

UNSIGNED_16