0x6071 | 0x6871 - torque demand, 0x6072 | 0x6872 - max torque, 0x2946:1 – Lenze i700 User Manual

Page 220: 0x3146:1, 0x2946:2, 0x3146:2, 0x2946, 0x3146, 0x6071, 0x6871

Advertising
background image

7

CiA402 device profile

7.10

Cyclic sync torque mode (cst)

220

Lenze · i700 servo inverter · Reference manual · DMS 1.5 EN · 03/2014 · TD05

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

0x2946 | 0x3146 - Cyclic sync torque mode: Speed limitation

0x6071 | 0x6871 - Torque demand

0x6072 | 0x6872 - Max torque

The torque control contains a speed limitation as a protective function against very high speeds. High speeds can

occur in the case of a mere torque selection if no counter-torque is available (load-free machine).

The speed limitation function takes effect if the actual motor speed reaches the limit values set here: The motor

speed is kept at the limit value in each case. If the machine is decelerated by a counter-torque again, the speed

limitation hands control back to the external setpoint via the setpoint torque.

Note!

The upper limit value must be set to a greater value than the lower limit value. There is no plausibility check in the

i700 servo inverter.

Sub.

Name

Lenze setting

Data type

1

Speed limitation: Upper speed limit

0 [n-unit]

INTEGER_32

2

Speed limitation: Lower speed limit

0 [n-unit]

INTEGER_32

Subindex 1:

Speed limitation: Upper speed limit

Upper limit for the speed limitation
Setting range

(min. value | unit | max. value)

Lenze setting

-480000

[n unit]

480000 0 [n-unit]

Write access  CINH  OSC  P  RX  TX

Scaling: 480000/2

31

INTEGER_32

Subindex 2:

Speed limitation: Lower speed limit

Lower limit for the speed limitation
Setting range

(min. value | unit | max. value)

Lenze setting

-480000

[n unit]

480000 0 [n-unit]

Write access  CINH  OSC  P  RX  TX

Scaling: 480000/2

31

INTEGER_32

Target torque or torque feedforward control

• 100 % ≡ rated motor torque (

0x6076

or

0x6876

for axis B)

Setting range

(min. value | unit | max. value)

Lenze setting

-3276.8

%

3276.7 0.0 %

Write access  CINH  OSC  P  RX  TX

Scaling: 1/10

INTEGER_16

Symmetrical selection of the maximum permissible torque

• 100 % ≡ rated motor torque (

0x6076

or

0x6876

for axis B)

• This parameter serves to implement a statically and bipolarly acting torque limitation. This can be used, for

instance, as overload protection of the mechanical transmission path/elements starting at the motor shaft.

• This limitation acts independently of the unipolarly acting torque limitations which act as process data on the

objects

0x60E0

(or

0x60E0

for axis B) and

0x60E1

(or

0x60E1

for axis B). For details see

signal flow

.

Setting range

(min. value | unit | max. value)

Lenze setting

0.0

%

3276.7 250.0 %

Write access  CINH  OSC  P  RX  TX

Scaling: 1/10

UNSIGNED_16