5

Motor control & motor settings

5.7

Compensating for inverter influence on output voltage

72

Lenze · i700 servo inverter · Reference manual · DMS 1.5 EN · 03/2014 · TD05

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

Preconditions for the execution

• The motor may be firmly braked.
• The controller is free of errors and is in the "

Switched on

" device status.

Response of the motor during the execution
If the motor is not firmly braked, it will move slightly.

How to determine the inverter characteristic:

1. If the controller is enabled, inhibit the controller.

Enable/inhibit operation via control word

( 59)

2. Set object

0x2825

(or

0x3025

for axis B) to "8" to change to the "Inverter characteristic:

Identification" operating mode.

3. Enable the controller to start the procedure.

Note: By means of controller inhibit, the started procedure can be cancelled any time.

Characteristic values that have already been determined are rejected in this case.

After successful completion...
...the controller will be inhibited automatically and the points of the determined inverter

characteristic will be set in object

0x2947

(or

0x3147

for axis B).

• For permanent storage, the changed settings must be uploaded to the controller from the i700

servo inverter.
The »EASY Starter« serves to save the parameter settings of the i700 servo inverter as parameter

file (*.gdc). In the »PLC Designer«, this file can then be imported in the corresponding axis.

Saving changed parameters safe against mains failure

( 60)

• The inverter characteristic must only be detected again if the controller, motor, or motor cable

has changed e.g. due to an exchange.

• The controller inhibit automatically set by the procedure can be deactivated via the

Controlword (

0x6040

or

0x6840

for axis B) (setting = 7, 15).

In the event of an error
If an error occurs during the procedure or the pulse inhibit gets active (e.g. due to short-time

undervoltage), the procedure is terminated with controller inhibit without a change in settings.