5.17

Setting the switching frequency

The i700 servo inverter can be operated with the switching frequencies listed below.

0x2939 | 0x3139 - Switching frequency

Note: In case of "8 kHz variable" and "16 kHz variable", variable switching frequencies are involved. If the

permissible continuous current for the respective switching frequency is exceeded, it is automatically switched back

to the next-lower switching frequency and vice versa.

For servo applications, we recommend, if possible, the operation with a fix switching frequency!

Selection list

(Lenze setting printed in bold)

Info

0 16 kHz variable

• Low operating noises of the motor but higher current

consumption during the acceleration phases.

• For operating motors which are designed for

switching frequencies > 8 kHz, e.g. milling drives and

mid-frequency motors.

1 8 kHz variable

• Reduced operating noises of the motor but higher

current consumption during the acceleration phases

compared to the operation with 4 kHz.

• E.g. for the operation of internally-ventilated

asynchronous servo motors.

2 4 kHz

• Servo applications with medium requirements or

control quality.

• V/f characteristic control

• Operation of motors which are designed for

switching frequencies of 3 to 6 kHz.

10 16 kHz fix

From version 01.06

• Servo application with highest requirements or

control quality.

• Operation of motors which are designed for

switching frequencies of 12 to 16 kHz, e.g. mid-

frequency motors.

• Low-noise operation of motors.

11 8 kHz fix

From version 01.06

• Servo application with high requirements or control

quality.

• Servo control SM with field weakening

• Operation of motors which are designed for

switching frequencies of 6 to 10 kHz.

Write access  CINH  OSC  P  RX  TX