5.11.5

Setting the field controller (ASM)

For motors with great rotor time constants or small rotor resistances, very high gain factors are

calculated. Since the setting range of the field controller is limited to the double rated magnetising

current, the field control loop in the case of these motors tends to a two-point response when the

values calculated are entered.

Tip!
Starting from a calculated gain factor of approx. 1000 A/Vs, do not set the full value

anymore.
Example: Calculated value = 10000 A/Vs  setting = 3000 A/Vs

For the automatic calculation of the controller parameters, the "Field controller: Calculate controller

parameters" function is provided via object

0x2822

(or

0x3022

for axis B).

0x29C0 | 0x31C0 - Field controller: Parameter

Equations for calculating the gain and the reset time

Axis A

Axis B

Symbol Description

Dimension unit

0x29C0:1 0x31C0:1

V

p

Field controller gain

A/Vs

0x29C0:2 0x31C0:2

T

n

Field contr. reset time

s

0x2C02:2 0x3402:2

L

h

Mutual motor inductance (ASM)

H

0x2C02:1 0x3402:1

R

r

Motor rotor resistance (ASM)

Ω

-

-

T

current

controller

Equivalent time constant of the current control loop

= 0.0005 s (500 μs)

s

-

-

T

r

Motor rotor time constant

-

-

K

path

Gain of the controlled path

-

-

L

r

Motor rotor inductance (ASM)

H

V

p

1

4 R

r

T

Current controller

----------------------------------------------------------

V

p

T

n

4 K

Distance

T

Current controller

---------------------------------------------------------------------------

L

r

R

r

-----

4 L

h

T

Current controller

----------------------------------------------------------

=

=

T

n

T

r

L

r

R

r

-----

=

=

Sub.

Name

Lenze setting

Data type

1

Field controller: Gain

165.84 A/Vs

UNSIGNED_32

2

Field controller: Reset time

15.1 ms

UNSIGNED_16

Subindex 1:

Field controller: Gain

Setting range

(min. value | unit | max. value)

Lenze setting

0.00

A/Vs

50000.00 165.84 A/Vs

Write access  CINH  OSC  P  RX  TX

Scaling: 1/100

UNSIGNED_32