5motor control & motor settings – Lenze i700 User Manual

Page 110

Advertising
background image

5

Motor control & motor settings

5.11

Setting control loops

110

Lenze · i700 servo inverter · Reference manual · DMS 1.5 EN · 03/2014 · TD05

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

6. Record the step response of the motor current with the oscilloscope function of the »PLC

Designer«/»EASY Starter«.

• Parameters to be recorded:

Actual D current (

0x2DD1:1

or

0x35D1:1

for axis B)

Setpoint D current (

0x2DD1:3

or

0x35D1:3

for axis B)

D voltage (

0x2DD7:4

or

0x35D7:4

for axis B)

• Oscilloscope settings: Sampling rate = 0.0625 ms; time base = 2 ... 5 ms

Alternatively, the step response of the motor current in the motor phase U can be

measured by means of an oscilloscope and clamp-on ammeter.

7. Evaluate the step response:

8. Adjust the gain and reset time of the current controller.
9. Repeat steps 3 ... 6 iteratively until the optimum step response of the motor current is

reached.

• In the optimised state the current rise time typically is 0.5 ... 1 ms.
• If the adjustment does not provide any satisfactory results, the current controller

feedforward control via object

0x2941

(or

0x3141

for axis B) can be activated

additionally. Then steps 3 ... 6 are to be repeated.

10. To stop the test mode:

• Inhibit controller.
• Set object

0x2825

(or

0x3025

for axis B) to "0" to change back to the CiA402 mode.

11. For permanent storage: Upload changed current controller parameters (

0x2942

or

0x3142

for axis B) from the i700 servo inverter into the Controller.
The »EASY Starter« serves to save the parameter settings of the i700 servo inverter as

parameter file (*.gdc). In the »PLC Designer«, this file can then be imported in the

corresponding axis.

Saving changed parameters safe against mains failure

( 60)

I

t

I

t

I

t

I

t

I

t

I

t

I

t

I

t

I

t

Vp < Vp opt.

Vp = Vp opt.

Vp > Vp opt.

Tn

<

T

n

opt.

Tn

=

T

n

opt.

Tn

>

T

n

opt.