4.5

Monitoring of the DC-bus voltage

For the device as a whole, the DC-bus voltage is monitored with regard to undervoltage and

overvoltage.

• The voltage monitoring is active in the device statuses "

Ready to switch on

", "

Switched on

",

"

Operation enabled

" and "

Quick stop is active

".

• The warning thresholds for the monitoring are adjustable and preset for a rated mains voltage

of 400 V in the Lenze setting.

• The error thresholds for the monitoring result from the set rated mains voltage:

0x2540 - Device: Voltage values

Mains

Undervoltage thresholds

Overvoltage thresholds

Rated

voltage

0x2540:1

Warning threshold

0x2540:2

Error threshold

0x2540:3

Threshold "Reset

error"

0x2540:4

Warning threshold

0x2540:5

Error threshold

0x2540:6

Threshold "Reset

error"

0x2540:7

60 V

430 V

10 V

15 V

795 V

60 V

50 V

230 V

eff

200 V

225 V

800 V

790 V

400 V

eff

285 V

430 V

800 V

790 V

480 V

eff

490 V

535 V

800 V

790 V

Greyed out = read access only or threshold specified

Sub.

Name

Lenze setting

Data type

1

Mains: Rated voltage

1: 400 Veff

UNSIGNED_8

2

Undervoltage (LU): Warning threshold

430 V

UNSIGNED_16

3

Undervoltage (LU): Error threshold

285 V

UNSIGNED_16

4

Undervoltage (LU): Threshold 'Reset error'

430 V

UNSIGNED_16

5

Overvoltage (OU): Warning threshold

795 V

UNSIGNED_16

6

Overvoltage (OU): Error threshold

800 V

UNSIGNED_16

7

Overvoltage (OU): Threshold 'Reset error'

790 V

UNSIGNED_16

Subindex 1:

Mains: Rated voltage

Selection of the mains voltage used with which the i700 servo inverter is operated.
Selection list

(Lenze setting printed in bold)

0 230 Veff
1 400 Veff
2 480 Veff
3 Reserved
4 60 V (setting-up operation)

Write access  CINH  OSC  P  RX  TX

UNSIGNED_8

Subindex 2:

Undervoltage (LU): Warning threshold

Warning threshold for monitoring with regard to undervoltage

• If the DC-bus voltage of the i700 servo inverter falls below the threshold value set here, the device reports a

warning. Reset is effected with a hysteresis of 10 V.

Setting range

(min. value | unit | max. value)

Lenze setting

0

V

800 430 V

Write access  CINH  OSC  P  RX  TX

UNSIGNED_16